UK Workplace Exposure Limits (EH40) for Common Gases: A Gas Detection Reference

Writer: Alex Graft
Alex Graft
5 days ago
3 min read

Updated: 4 days ago

Workplace exposure limits (WELs) are legally binding limits on the concentration of hazardous substances in workplace air, where they apply under the Control of Substances Hazardous to Health Regulations (COSHH) in Great Britain. They are published by the Health and Safety Executive in EH40/2005 Workplace exposure limits. The figures below are from the fourth edition, published in January 2020, with its changes taking effect on 17 January 2020; check HSE's EH40 page for the current published version. HSE is clear that WELs are only one part of COSHH: meeting a limit does not replace the duty to prevent or adequately control exposure. EH40 does not set gas detector alarm levels; alarm settings are a separate decision based on your risk assessment, the purpose of monitoring and what the instrument can measure.

Two limits: 8-hour TWA and 15-minute STEL

Each WEL can have two values. The long-term limit is an 8-hour time-weighted average (TWA): the average exposure across a working shift. The short-term exposure limit (STEL) is a 15-minute average, which controls brief peaks. Many personal gas monitors calculate running TWA and STEL readings alongside instantaneous low and high alarms. An instantaneous alarm reacts to the concentration at that moment; it does not measure an 8-hour or 15-minute average, so an alarm set at a WEL does not on its own show that exposure is within the limit.

EH40 limits for common gases (ppm)

  • Ammonia (NH3): 25 ppm TWA, 35 ppm STEL

  • Carbon dioxide (CO2): 5,000 ppm TWA, 15,000 ppm STEL

  • Carbon monoxide (CO): 20 ppm TWA, 100 ppm STEL for general workplaces (EH40 lists separate values for underground mining and tunnelling)

  • Chlorine (Cl2): 0.5 ppm STEL (no 8-hour limit)

  • Chlorine dioxide (ClO2): 0.1 ppm TWA, 0.3 ppm STEL

  • Hydrogen chloride (HCl): 1 ppm TWA, 5 ppm STEL

  • Hydrogen cyanide (HCN): 0.9 ppm TWA, 4.5 ppm STEL

  • Hydrogen fluoride (HF): 1.8 ppm TWA, 3 ppm STEL (expressed as F)

  • Hydrogen peroxide (H2O2): 1 ppm TWA, 2 ppm STEL

  • Hydrogen sulphide (H2S): 5 ppm TWA, 10 ppm STEL

  • Nitrogen monoxide (nitric oxide, NO): 2 ppm TWA (EH40 lists a separate 25 ppm limit for underground mining and tunnelling)

  • Nitrogen dioxide (NO2): 0.5 ppm TWA, 1 ppm STEL

  • Ozone (O3): 0.2 ppm STEL

  • Phosphine (PH3): 0.1 ppm TWA, 0.2 ppm STEL

  • Sulphur dioxide (SO2): 0.5 ppm TWA, 1 ppm STEL

  • Benzene: 1 ppm TWA, no STEL listed (marked Carc in EH40: exposure must be controlled as low as is reasonably practicable)

Where EH40 lists no STEL, it says a figure of three times the long-term limit should be used to control short-term exposure (EH40, paragraph 14). So a blank STEL does not mean there is no short-term limit to consider: for benzene, with a 1 ppm 8-hour limit and no listed STEL, the three-times rule applies. See the EH40/2005 publication.

Always check the current edition of EH40 on the HSE website before relying on a figure for compliance, as limits are revised from time to time.

Oxygen and flammable gases are different

Oxygen and flammable gases do not have WELs, and EH40 does not set alarm levels for them. Oxygen monitors alarm on deficiency and enrichment: typical settings are 19.5% and 23.5% by volume (normal air is 20.9%). Flammable gas is measured as a percentage of the lower explosive limit (LEL), with typical alarm settings of 10% and 20% LEL. The right values depend on the applicable site standard and your risk assessment.

General guidance for gas detector users

  • These points are general guidance, not EH40 requirements.

  • Base alarm settings on your risk assessment, the purpose of monitoring and the instrument's capability. Instantaneous alarms are not interchangeable with the monitor's TWA and STEL calculations or with a proper exposure assessment.

  • Choose sensors with a range and resolution suited to low limits: chlorine dioxide, phosphine and nitrogen dioxide need low-range sensors.

  • Follow the detector manufacturer's recommendations for bump testing and calibration. Many manufacturers recommend a bump test before each day's use; calibration intervals vary by instrument and use, and six months is common.

  • Record exposure data where your COSHH assessment requires monitoring.

7 Solutions supplies, hires and calibrates portable and fixed gas detectors and can set alarms to the levels your risk assessment specifies. Call 01489 326031, or see gas detector hire and calibration and service.

 
 
 